All chapters

Event reference

Every reading, report, alarm code and detection becomes an event described by the same five facts. Huntress maps about 250+ SIA DC-03 codes and 230+ Contact ID codes onto this vocabulary.

Domain#

What kind of situation the event is about.

Domains
DomainCovers
IntrusionBurglary, motion, glass break, entry and perimeter alarms.
FireSmoke, heat, flame and fire panel events.
MedicalMedical and personal-emergency calls.
PanicHold-up, duress and panic alarms, including a person's panic button.
Access controlDoors, gates, request to exit, forced and held-open doors.
EnvironmentalTemperature, humidity, water, gas, air and other measurements and hazards.
SystemPower, communication, tamper, battery and other health of a device or panel.
AutomationWhat Huntress itself did: a limit crossed, a schedule switching, a command issued.
VideoCamera analytics and detections.
Open / closeArming and disarming a panel or area.
PersonReports from a tracked person.
UnknownA payload that could not be classified; it is stored as received.

Nature#

What the event does to the situation. A restore cancels the alarm it follows.

Natures
NatureMeaning
AlarmSomething that needs attention has happened.
RestoreThe condition has ended (a door closed, a zone restored, a value back inside its limit).
TroubleA fault: a battery low, a line cut, a device failing.
BypassA zone was bypassed or unbypassed.
TestA test report.
StatusInformation that is neither an alarm nor a fault.
CommandA command was issued to an output.
Open / closeAn arming or disarming.

Severity#

Severities
SeverityUse
CriticalLife safety or an immediate, serious threat: a panic alarm, a verified fire.
HighA likely real alarm: burglary, fire, a person detected.
MediumNeeds a look: tamper, a limit crossed, a fault.
LowMinor or informational faults.
InfoRoutine: keepalives, restores, openings and closings.

Alarm-panel codes#

How to read the tableSIA alarm or trouble codes make the event. SIA restore codes cancel an alarm, shown as RestoreCode→AlarmCode (BR→BA: BR restores BA). SIA other codes are bypass, test and status, with the first letter of their nature in brackets. Contact ID's nature comes from its qualifier: 1 for a new event, 3 for a restore, 6 for a previously reported one. A star marks a verified alarm: the incident is raised to confidence C5.
Event types with the SIA and Contact ID codes that produce them
Event type Domain Severity SIA alarm / trouble SIA restore (→ cancels) SIA other Contact ID
AccessDenied AccessControl Medium CA, CF — CB(B), KB(B), KU(S) 421, 436, 461, 501, 503, 507, 514, 515
DoorForcedOpen AccessControl High CD — — 423, 432, 434
DoorHeldOpen AccessControl Medium CG, CH, CK — — 426, 427
RequestToExit AccessControl Medium — — — 424, 425, 428, 433
ValidAccess AccessControl Info — CC, CJ, CR, KC CE(S), CL(S), CO(S) 422, 435, 462
CODetected Environmental Critical CN — — 112, 162, 394
FloodDetected Environmental High WA, WH WJ→WA, WR→WA WB(B), WU(S), WX(T) —
GasDetected Environmental Medium GA, GH, GS GJ→GA, GR→GA GB(B), GU(S), GX(T) 151
HighTemp Environmental Medium — — — 152, 158
LowTemp Environmental Medium — — — 153, 159
ThresholdExceeded Environmental Medium EA, EH, ES, ET, NA, NH EJ→EA, ER→EA, NJ→NA, NR→NA EB(B), EU(S), EX(T), NB(B) 150, 157, 161, 163, 168, 169
WaterFlow Environmental Medium WS — — 113, 201, 204
WaterLeak Environmental Medium — — — 154
FireAlarm Fire Medium FA, FG, FS FC→FA, FJ→FA, FL→FA, FR→FA FB(B), FU(S), FX(T) 110, 115, 116, 118, 200, 202, 203, 604, 614
FireVerified Fire Critical FM, FV — — —
FlameDetected Fire Critical — — — 117
HeatDetected Fire Critical FH — — 114
SmokeDetected Fire Critical FK — — 111
SprinklerActivated Fire High FQ — — 205
BurglaryAlarm Intrusion Medium AA, AU, BA, BE, LA, LH BC→BA, BH→BA, BJ→BA, BR→BA, LJ→LA, LR→LA BB(B), BD(B), BU(S), BX(T), LB(B), LU(S), LX(T) 130, 131, 133, 134, 135, 136, 138, 140, 146, 155, 374, 406, 457, 506, 509, 510, 511, 512, 513, 516, 613
BurglaryVerified Intrusion Medium BG, BM, BV — — 139
ZoneFault Intrusion Low BS, BT, BZ, FT, FZ, GT, GZ, HT, HZ, LS, LT, MT, NT, PT, WT, XZ, ZA, ZH, ZS, ZT ZJ→ZA, ZR→ZA ZB(B), ZU(S), ZX(T) 141, 142, 147, 156, 206, 320, 321, 322, 331, 332, 370, 371, 372, 373, 375, 376, 377, 378, 380, 381, 382, 386, 387, 388, 389, 391, 392, 393, 502, 532, 641
MedicalAlarm Medical Medium MA, MH, MS MJ→MA, MR→MA MB(B), MU(S), MX(T) 100, 101, 102
ArmedAway OpenClose Info — — OJ(O), OS(O), OU(S) 400, 402, 403, 407, 408, 409, 443, 450, 452, 459
ArmedStay OpenClose Info — — — 405, 441, 442, 456
DisarmedByUser OpenClose Info — — OC(O), OG(O), OH(O), OI(O), OK(O), OP(O), OR(O) 401, 451, 458, 463
FailToClose OpenClose Medium — — — 453, 454
LateToArm OpenClose Low OT — OA(S), OL(S) 404, 455, 464
AudiblePanic Panic Critical AB, PA, PH PJ→PA, PR→PA PB(B), PU(S) 120, 123, 465, 615
DuressAlarm Panic Medium CQ, DA, DG, DH, DS, DT DJ→DA, DR→DA DB(B), DU(S), DX(T) 121, 124, 125
SilentPanic Panic Medium HA, HH, HS, HV, PS HJ→HA, HR→HA HB(B), HU(S), HX(T) 122, 534
CommFailure System Low CI, YA, YC, YF, YG, YH, YK, YM, YP, YS, YT, YW, YZ — YB(B), YX(T) 347, 348, 349, 350, 351, 352, 353, 354, 355, 356, 357
CommRestored System Info — YR→YA — —
LowBattery System Medium — — — 302, 309, 311, 342, 385
MainsFailure System Medium AT — — 301, 310, 312, 314, 341, 345
MainsRestored System Info — AR→AT — —
PanelTamper System Medium CT, KA, KH, KS, KT KJ→KA, KR→KA — 316, 317
ScheduleChanged System Low — — — 306, 524, 525, 529, 530, 531, 625, 626, 631, 632
SelfTestFail System Medium SA, SS, ST, XA, XH, XS, XT SR→SA, XJ→XA, XR→XA SB(B), SU(S), XB(B), XU(S), XX(T) 143, 300, 303, 304, 305, 307, 308, 313, 315, 330, 333, 334, 335, 336, 343, 346, 390, 504, 608
ZoneTamper System Low AS, JA, JH, JT, TA, TS, TT, TZ JR→JA, TJ→TA, TR→TA TB(B), TU(S), TX(T) 137, 144, 145, 344, 383, 384, 505
CameraOnline Video Medium VL, VS, VT VR→VL VU(S), VX(T) 609
CameraTamper Video Low CM, VI, VZ — — —
LineCross Video Medium VY — — —
MotionDetected Video Medium IA, IH, VM IJ→IA, IR→IA IB(B) 132
UnknownEvent System Info QA, QH, QS, QT, RS, RT, UA, UH, US, UT, UZ QJ→QA, QR→QA, UJ→UA, UR→UA AN(S), QB(B), QU(S), QY(S), RA(S), RB(B), RN(C), RO(C), RR(S), RX(T), RY(S), UB(B), UU(S), UX(T) 411, 412, 413, 414, 415, 416, 429, 430, 431, 466, 508, 520, 521, 522, 523, 526, 527, 528, 533, 601, 602, 603, 605, 606, 607, 611, 612, 616, 621, 622, 623, 624, 627, 628, 642, 654

Person events#

Reported by Pulse or any client of the Hunt API with an eventType. They are first-class event types, not panel codes.

Person events
Event typeDomainNatureSeverity
MovementPersonStatusInfo
KeepalivePersonStatusInfo
PanicAlarmPanicAlarmCritical
Connection lost